10kv zinc lighting arrester

product details

Main Principle:


* ZnO lighting arrester is one kind most world advaned over-voltage protector at present.Due to its core components of resistance applying ZnO and other metal oxide to make of comparing with traditional craborundum    arrester.it improves greatly V-A characteristics of resistance,increases the getting trough ability of  resistance,there by it brings fundamental change to features of arrester. 


* Under normal working vlotage,the current passing arrester only A class,when bearing over voltage ,the    excellent nonlinear V-A features of arrester would make effect,the current passing through the arrester  increase high to shousands of ampere instant,the arrester is under getting through state to release over-  voltage enrgy,there for it effective limits the damage to power transmission equipments due to over voltage.


Usage& feature:


   ZnO Lighting Arrester is one kind protecting equipment preventing electric equipments in AC power system from  high voltage and over-voltage operation.


Using Environments:


* Ambient temperature no higher than +40℃,no less than -40℃;

* Above sea level no higher than 1000m(order should be indicated if used in tableland area);

* Power frequency not less than 48HZ and no higher than 62HZ;

* Continuous power frequency voltage loaded on lightning arrester no higher than continuous working voltage of lightning arrester;

* Utmost wind volocity no higher than 35m/s;

* Area where earthquake intensity less than 7 degree;

* Messy area should be indicated;


  Our make product voltage range:0.22kV ~110kV.

  Our factory make this product sinc July.2000.we accept OEM and ODM,you have drawing or spec,we all can help you to make and design it.our product used for more country line and station project(such as greece,tanzania,chile,philippinesetc).



Using AreaPower distribution(S)
ModelHY5WS-16.5/50LHY5WS-17/50LHY5WS-17.5/50L
lighting arester rating voltage virtual value(kV)16.51717.5
System nominal voltage virtual value(kV)101010
Continuous working voltage virtual value(kV)12.713.613.6
DC(U1mA) Rel.Voltage no less than (kV)252525
Max residual voltage peak value(kV)Teep wave impulse current 57.557.557.5
Lighting impulse current505050
Operating impulse current42.542.542.5
2000µs square wave flux capacity(A)757575
4/10µs impulse current peak value(kA)404040
Max.Leaking current under 0.75DC ref.Voltage(µA)303030